Descrizione
This manual call point “break glass” type is designed for corrosive environments and dedicated for the Oil & Gas, chemical, petrochemical, pharmacy industries, marine and offshore applications.
The product is compatible with PLC, ESD, DCS systems via an output 4-20mA.
The housing moulded in glass-reinforced polyester is dyed in the mass and protected with a UV resistant paint.
Optionally: visualisa1ion functions, line detection, glass protection and hammer.
Other accessories to customize the products are available.
MATERIAL ENCLOSURE: Glass-reinforced polyester (GRP)
COLOR: RED: RAL3001 – YELLOW**: RAL1018 – BLUE**: RAL5005 – BLACK**: RAL9004
IP RATING: IP66/67
AMBIENT TEMPERATURE: -40°C +70°C
CERTIFICATES: ATEX – IECEX
MARKING: II2GD Exd IIC T4…T6 Gb Ex tb IIIC T135°C (Tamb = -40″C…+70°C)
AMBIENT HUMIDITY*: UNTIL 95% WITH ICE
RATE IMPULSE WITHSTAND VOLTAGE: 1kV according to IEC 61000-4-5
CONTACT TYPE: 1 x C/O or 2 x C/O**
CONVENTIONAL THERMAL COURANT (lth): AC 125/250V (50/60Hz)=11A*** ; 30V DC=6A*** ; 125V DC=0.3A***
MINIMUM VOLTAGE AND COURANT: DC 5V l0mA
SHORTS CIRCUIT PROTECTION: lOA gG
CABLE ENTRIES: 4xM20, M25**, l/2″NPT**, 3/4″NPT or other**(Specify)
TERMINAL: From 22 to 14AWG – From 0.5mm2 to 2.5mm2
NET WEIGHT: 4,2kg
LINE RESISTOR**: 470 Ohms
SIGNALLING LED**: Green U=24V DC I= lOmA ; Red U=24V DC I= 20mA
*=without runoff – **=optional – ***=resistive load – coble gland and blind plug not provided